In a current differential protection scheme, current transformers (CTs) are used to measure the current entering and leaving a protected zone, such as a transformer, busbar, or transmission line. The differential protection operates by comparing the current measured by CTs at different locations. Ideally, the current flowing into the zone should be equal to the current flowing out if there is no fault. However, if there is a mismatch in the CT ratio, the measured currents may not be exactly equal, even during normal operation, which could result in a false differential current and, therefore, an unwanted trip.
### Understanding the Problem of CT Ratio Mismatch
CT ratio mismatch occurs when the ratio of the CTs on either side of the protected zone is different or when there are slight inaccuracies due to manufacturing tolerances, aging, or saturation effects. Since differential protection works by comparing currents, a mismatch in the CT ratio could cause incorrect operation.
For example, consider a transformer protection scheme with CTs installed on both the primary and secondary sides of a power transformer. Because the current on the primary side is different from the current on the secondary side (due to the transformer turns ratio), CTs with different ratios are used on each side. Any error in matching these CT ratios could create an artificial differential current, leading to mal-operation.
### How Current Differential Protection Handles CT Ratio Mismatch
Several techniques are used in differential protection schemes to address CT ratio mismatch and prevent false tripping:
#### 1. **Use of Matching CT Ratios and Proper Sizing**
The simplest solution is to ensure that CTs are properly selected with matching or proportional ratios that correspond to the current on each side of the protected zone. For example, if one side of the transformer has a CT with a ratio of 1000:1 (primary to secondary), the other side should have a CT with a ratio that is scaled appropriately based on the transformer's turns ratio, such as 100:1 for a 10:1 transformer ratio. This ensures that the measured secondary currents from both CTs are proportional.
#### 2. **Ratio Correction via Relay Settings**
Modern digital relays used in current differential protection schemes have built-in ratio correction features. These relays allow the user to input the CT ratios for the primary and secondary sides. The relay automatically adjusts the measured current values by scaling them according to the CT ratios. This way, any inherent mismatch in the CTs is compensated digitally, and the relay can compare the corrected values for accurate differential protection.
For example, if one CT has a 1000:1 ratio and the other has a 200:1 ratio, the relay can internally scale the currents to make them comparable by multiplying the measured current of the second CT by 5 (the ratio between 1000:1 and 200:1).
#### 3. **Percentage (Biased) Differential Protection**
Percentage differential protection is designed to handle small discrepancies due to CT ratio mismatch and other minor errors. Instead of tripping for any small differential current, this method introduces a bias or restraint characteristic. The protection relay calculates the average of the current flowing into and out of the protected zone and sets a threshold based on the magnitude of these currents.
In other words, the greater the current flowing through the protected zone, the larger the differential current that is tolerated without causing a trip. This bias helps prevent unnecessary trips due to minor CT inaccuracies or ratio mismatches during normal load conditions.
The differential current (I_diff) and bias current (I_bias) are calculated as follows:
- **I_diff = (I1 - I2)**
- **I_bias = (I1 + I2) / 2**
Where:
- I1 is the current from the first CT.
- I2 is the current from the second CT.
The relay uses a predefined slope or percentage bias characteristic to determine whether the differential current is large enough to trigger a trip. If the differential current exceeds a certain percentage of the bias current, the relay operates.
#### 4. **Dual-Slope Characteristic**
Many modern relays use a dual-slope characteristic in the percentage differential protection scheme to better handle CT ratio mismatch, CT saturation, and external faults. The first slope is applied for lower levels of bias current, and a second, steeper slope is applied for higher levels of bias current.
This approach allows the protection to be more sensitive at lower current levels (where CT mismatch is less likely to be significant) while being more tolerant at higher current levels (where CT mismatch or saturation could be more pronounced).
#### 5. **CT Saturation Detection and Compensation**
In high-current fault scenarios, CTs can become saturated, which can exacerbate the mismatch between the currents from the two sides of the protected zone. To address this, modern relays have algorithms that detect CT saturation and prevent tripping during these conditions.
For example, when CT saturation is detected, the relay can temporarily desensitize or restrain the differential protection until the CTs recover, ensuring that the protection does not operate incorrectly due to distorted current waveforms.
#### 6. **Supervision of Differential Current**
Another way the protection scheme handles CT ratio mismatch is through supervision of the differential current. This supervision can include checks such as:
- **Zero-sequence filtering**: Removes false differential current caused by ground current or unbalanced load.
- **Harmonic restraint**: Detects harmonics in the differential current during transformer energization, preventing mal-operation due to inrush currents (which are rich in second harmonic components).
### Example of a Protection Scenario
Consider a 132 kV to 33 kV transformer protected by differential relays. The CT ratio on the 132 kV side is 800:1, and on the 33 kV side, it's 400:1. There’s a slight mismatch due to differences in CT saturation characteristics or inaccuracies. To handle this:
- The relay scales the currents from the 33 kV side by 2 to match the 132 kV side.
- A percentage bias protection is applied, allowing a small margin for error in the measured current.
- If there's a slight difference in current due to the mismatch, the bias will prevent a trip as long as the difference is within an acceptable range.
### Conclusion
A current differential protection scheme handles CT ratio mismatch through a combination of proper CT selection, digital ratio correction in relays, percentage bias protection, and supervision techniques. These measures ensure that the protection scheme operates reliably, avoiding false tripping due to minor mismatches, while still being sensitive to real internal faults.