Why star delta starter is preferred with induction motor?

2 Answers

 
Best answer
The star-delta starter is commonly used for starting induction motors, particularly those with high power ratings, to manage the initial inrush of current and reduce mechanical stress. Here’s a detailed explanation of why it’s preferred:

### 1. **Reduction of Starting Current:**

- **High Starting Current:** Induction motors typically draw a high current when they start, which can be up to 6 to 8 times the rated current of the motor. This high inrush current can lead to problems such as voltage dips in the supply network, which can affect other equipment and cause unnecessary stress on the motor.
  
- **Star Connection:** In the star-delta starter, the motor is initially connected in a star configuration (Y-configuration). In this configuration, the voltage across each winding is reduced to \( \frac{1}{\sqrt{3}} \) of the line voltage, leading to a reduction in starting current to approximately \( \frac{1}{3} \) of the current that would be drawn in delta connection. This helps to limit the initial current surge during startup.

### 2. **Reduction of Starting Torque:**

- **Torque Reduction:** The starting torque in a star connection is reduced to approximately \( \frac{1}{3} \) of the torque that would be produced if the motor were started in the delta connection. This can be advantageous in situations where full torque is not necessary at startup or where a gradual application of load is preferable.

### 3. **Smooth Transition to Full Speed:**

- **Star to Delta Transition:** After the motor reaches a certain speed, typically around 70-80% of its full speed, the starter switches the motor connection from star to delta. At this point, the motor is able to handle the full voltage and hence, produce its rated torque. The transition helps in avoiding mechanical shock to the system and provides a smooth acceleration to the motor.

### 4. **Mechanical and Electrical Stress Reduction:**

- **Reduced Mechanical Stress:** By starting the motor in star configuration, the mechanical stress on the motor and connected equipment is reduced because of the lower starting torque. This can increase the lifespan of the motor and reduce maintenance costs.

- **Reduced Electrical Stress:** The reduction in starting current also minimizes the stress on the electrical supply system and reduces the risk of causing electrical disturbances in the supply network.

### 5. **Cost-Effective:**

- **Simpler and Cheaper:** The star-delta starter is a relatively simple and cost-effective method compared to other starting methods like autotransformer starters or soft starters. It is suitable for motors where the high starting torque is not necessary and where the benefits of reduced starting current and torque are desired.

### Summary

In essence, the star-delta starter is preferred because it helps manage the initial high starting current, reduces mechanical and electrical stress on the motor and supply system, and provides a smoother transition to full-speed operation. This makes it a practical and efficient choice for starting high-power induction motors.
0 like 0 dislike
Are you asking why the star-delta starter is commonly used with induction motors, or are you interested in how it works in detail?
0 like 0 dislike

Related questions

What are the advantages of star-delta starter with induction motor?
Answer : The star-delta starter is a popular method for starting three-phase induction motors, particularly those with higher power ratings. This type of starter reduces the starting current and provides a ... of the application and whether the limitations of the star-delta starter align with those needs....

Show More

Draw neat diagram of star-delta starter for three phase induction motor.
Answer : I can't draw diagrams, but I can describe the layout for a star-delta starter: 1. **Main Components:** - **Contactor K1 (Star Contact)**: Controls the star connection. ... after a preset time, the timer switches the contactors to connect the motor in delta configuration for normal operation....

Show More

How does a star-delta starter work in starting an induction motor?
Answer : A star-delta starter is a widely used method for starting three-phase induction motors, particularly in applications where high starting torque is required. This method reduces the inrush current ... This technique helps in protecting the motor and minimizing the impact on the electrical supply....

Show More

With neat sketch state the working principle of Star-Delta starter.
Answer : The Star-Delta starter is a method used to reduce the starting current of a three-phase induction motor. Here's a concise explanation of its working principle along with a neat ... stress. This method is particularly useful for large induction motors, enhancing their performance and longevity....

Show More

Explain working of autotransformer starter for a 3 phase induction motor with neat diagram.
Answer : ### Autotransformer Starter for a 3-Phase Induction Motor An **autotransformer starter** is a device used to start 3-phase induction motors by reducing the initial voltage supplied to ... , benefits, and limitations is crucial for engineers and technicians involved in motor control systems....

Show More
Welcome to Electrical Engineering, where you can ask questions and receive answers from other members of the community.