A **Voltage Dependent Negative Sequence Overcurrent (VNSOC)** protection scheme is primarily used in power systems to detect unbalanced faults, such as line-to-line faults, line-to-ground faults, or phase loss, which can lead to negative-sequence currents in electrical machines or the system. This protection scheme is particularly sensitive to unbalanced conditions and is employed to protect generators, motors, transformers, and other equipment from thermal damage caused by prolonged unbalanced conditions.
### Key Concepts
Before diving into how the protection scheme works, it's important to understand some of the core concepts:
1. **Negative Sequence Components:**
- In a balanced three-phase system, the three phases (A, B, and C) are of equal magnitude and spaced 120Β° apart. When an unbalanced fault occurs (like phase-to-phase, phase-to-ground, or phase loss), the symmetry of the three-phase system is disturbed.
- This results in the appearance of **negative-sequence currents**. These currents represent an unbalanced condition where the sequence of the phases is in the opposite direction to the normal (positive) sequence. The negative-sequence currents can cause heating in generators, motors, and transformers, particularly in the rotor circuits.
2. **Voltage Dependency:**
- In a voltage-dependent scheme, the operating threshold of the protection system is influenced by the magnitude of the system voltage. This is important because during a fault, system voltage can drop, and the negative sequence overcurrent threshold may need to be adjusted to ensure the system operates appropriately based on the actual fault conditions.
3. **Overcurrent Protection:**
- **Overcurrent protection** detects abnormally high currents and operates to disconnect faulty equipment or sections of the system. In the case of negative-sequence overcurrent protection, the system detects high levels of negative-sequence current (indicative of unbalance), which can occur during faults or system abnormalities.
### How the Voltage Dependent Negative Sequence Overcurrent Protection Scheme Works
1. **Fault Detection via Negative Sequence Currents:**
- The protection relay continuously monitors the three-phase currents (IA, IB, IC) in the system.
- Using symmetrical component theory, the relay calculates the **negative-sequence current component (I2)** from the phase currents.
- Negative-sequence current is typically small during normal operation but becomes significant during an unbalanced fault condition (e.g., line-to-ground, line-to-line faults).
2. **Monitoring the System Voltage:**
- In addition to monitoring the currents, the relay also measures the system voltage. During a fault, the system voltage can drop significantly.
- The protection scheme becomes **voltage dependent** because it adjusts its sensitivity based on the voltage magnitude. If the voltage drops, the relay might lower the threshold at which it operates to detect the negative-sequence current.
3. **Decision Making and Operation:**
- The VNSOC scheme has a predefined pickup level for negative-sequence current (I2). However, this threshold is adjusted dynamically based on the system voltage.
- Under normal voltage conditions (close to nominal voltage), the relay operates based on a set I2 threshold.
- When the system voltage drops during a fault, the relay becomes more sensitive by lowering the pickup value of I2. This allows the relay to operate faster or at a lower current level during low-voltage conditions.
4. **Overcurrent Protection Action:**
- If the relay detects that the negative-sequence current exceeds the adjusted threshold, it sends a signal to trip the circuit breaker, isolating the faulted section of the system.
- The tripping could be instantaneous if the current exceeds the set limit by a significant margin, or it could be time-delayed if the current is only marginally above the threshold.
### Components of a VNSOC Scheme
- **Current Transformers (CTs):** Measure the line currents.
- **Voltage Transformers (VTs):** Measure the line voltages.
- **Relay:** A microprocessor-based protection relay that calculates the negative-sequence current and voltage, applies the voltage-dependent algorithm, and decides whether to trip the breaker.
- **Circuit Breaker:** Operates to isolate the faulty section when a trip signal is received from the relay.
### Key Benefits of the VNSOC Scheme:
1. **Enhanced Sensitivity to Unbalanced Faults:**
- The scheme is specifically sensitive to unbalanced faults and can detect conditions that may be missed by conventional overcurrent protection.
2. **Protection During Low Voltage Conditions:**
- Voltage dependency allows the relay to adapt to varying system conditions, such as when the voltage drops during a fault, ensuring effective protection even in low-voltage scenarios.
3. **Improved Equipment Protection:**
- Negative-sequence currents can cause overheating and damage to equipment like generators and motors. By detecting these currents, the scheme provides enhanced protection against thermal stress.
### Example of Application:
In large generators, which are sensitive to unbalanced currents, a VNSOC protection scheme is vital. A generator experiencing a phase-to-phase fault will have a high negative-sequence current that can cause rotor overheating and eventual damage. A VNSOC relay will detect the rise in negative-sequence current, especially under low-voltage conditions, and trip the generator before it sustains serious damage.
### Conclusion
A **Voltage Dependent Negative Sequence Overcurrent Protection Scheme** works by monitoring both the negative-sequence current and system voltage to protect power system components from unbalanced faults. By adjusting the protection thresholds based on system voltage, the scheme ensures reliable operation even during voltage dips caused by faults. This provides an additional layer of protection, particularly for generators, motors, and transformers, against the damaging effects of negative-sequence currents.