A Voltage Controlled Directional Comparison Scheme is a protection method used in electrical power systems, particularly in high-voltage transmission lines, to detect and isolate faults. This scheme uses voltage and current measurements from both ends of a transmission line and compares the direction of the fault current to ensure protection of the system. Let’s break down how it works step by step:
### 1. **Basic Components**
- **Voltage Relays**: These devices measure the voltage at the relay location. If the voltage decreases to a specific level (below a threshold), the relay assumes that a fault is present.
- **Directional Overcurrent Relays**: These relays determine the direction of the fault current. They use both current and voltage to establish whether the fault is upstream or downstream.
- **Communication Channel**: A critical part of the scheme, this connects relays on both ends of the transmission line, allowing them to exchange information about fault conditions.
### 2. **Key Concepts**
- **Fault Current**: When a fault (like a short circuit) occurs on a transmission line, a large current flows through the line. This is called fault current.
- **Directional Comparison**: The main idea here is to compare the direction of the fault current at both ends of the transmission line. If both relays sense the fault current flowing towards the line, they conclude that the fault is on that particular line.
### 3. **Directional Relay Operation**
Directional relays distinguish whether the fault is inside or outside the protected zone. The "zone" here refers to the section of the power system the relay is responsible for. If the fault is within this zone, the relay trips (disconnects) the circuit breakers to isolate the fault. If the fault is outside the zone, the relay doesn’t take action.
- **Forward Direction**: If the fault current is flowing into the protected line from the relay’s location, the fault is in the forward direction.
- **Reverse Direction**: If the fault current is flowing out of the protected line (towards the relay’s location), it indicates a fault in the reverse direction or on a neighboring line.
### 4. **Voltage Control**
In a Voltage Controlled Directional Comparison Scheme, voltage plays a crucial role in determining when to use the directional feature of the relay.
- **High Voltage (Normal Condition)**: Under normal operating conditions, the system voltage remains high, and there’s no need for protection action.
- **Low Voltage (Fault Condition)**: When a fault occurs, the voltage in the system drops significantly. The relays are designed to sense this drop. Once the voltage falls below a set threshold, the directional relays become active. They begin to monitor the current direction to detect the fault’s location.
### 5. **Fault Detection and Comparison Process**
Here’s how the scheme works during a fault:
#### Step 1: **Fault Occurrence**
A fault happens somewhere on the transmission line. This causes a large fault current to flow, and the system voltage drops at the fault location.
#### Step 2: **Relay Activation**
When the voltage drops below the predetermined threshold, the voltage relays at both ends of the line activate the directional overcurrent relays. These relays start monitoring the current’s direction.
#### Step 3: **Directional Comparison**
Each relay determines the direction of the fault current (whether it is flowing towards or away from the relay). The two relays at either end of the line communicate with each other to exchange their findings:
- **If both relays detect the fault current flowing towards the line**, they conclude the fault is within the protected zone.
- **If one relay detects the fault current flowing away from the line**, this indicates that the fault is outside the protected zone.
#### Step 4: **Decision and Trip Signal**
- If both relays agree that the fault is within the line (current flowing towards the line at both ends), they issue a trip command. This opens the circuit breakers, disconnecting the faulty section of the line from the system.
- If the relays determine that the fault is outside the protected zone, no action is taken, preventing unnecessary disconnection of the line.
### 6. **Communication**
To perform the directional comparison, the relays at both ends of the line need to exchange information quickly. This communication is done through a dedicated communication channel, like fiber optics, microwave links, or power-line carriers. Fast and reliable communication ensures that faults are cleared as quickly as possible, minimizing damage and system disturbance.
### 7. **Time Coordination**
In some cases, time delays are introduced to prevent false tripping. For instance, if the relays are unsure about the fault’s location or the communication is momentarily disrupted, they might wait for a small time interval (milliseconds) before making the final trip decision. This ensures that the relays trip only for genuine faults within the protected line.
### 8. **Advantages**
- **Selective Tripping**: The scheme ensures that only the section of the line where the fault occurred is disconnected, minimizing disruption to the rest of the power system.
- **Fast Operation**: The use of communication allows for quick fault detection and isolation, which is crucial for protecting high-voltage transmission lines.
- **Stable Under Normal Conditions**: The voltage control feature ensures that the directional comparison only activates during fault conditions, preventing unnecessary tripping.
### 9. **Limitations**
- **Communication Dependency**: The scheme relies on a fast and reliable communication link. If the communication fails, the protection may be delayed or ineffective.
- **Complexity**: The directional comparison scheme is more complex to set up and maintain compared to simpler protection methods, requiring careful calibration and testing.
### Conclusion
The Voltage Controlled Directional Comparison Scheme is a sophisticated protection strategy used to quickly and accurately detect and isolate faults in high-voltage transmission lines. It relies on the combination of voltage sensing, directional relays, and communication between relays to ensure that only the faulted section of the system is disconnected, ensuring the stability and safety of the overall power system.