### High Impedance Differential Protection (HIDP) and Current Transformer (CT) Saturation
#### **Understanding HIDP**
High Impedance Differential Protection (HIDP) is a type of differential protection scheme used to protect equipment like transformers, busbars, and generators. In a differential protection scheme, the current entering and leaving a protected zone (like a transformer winding or bus) is measured, and the difference between them (called differential current) is used to detect faults within the protected zone.
HIDP is specifically designed to handle a few key challenges, particularly **CT saturation**, which is a common issue in electrical systems.
#### **CT Saturation: What It Is and Why It's a Problem**
**CT saturation** occurs when the current transformer (CT) is exposed to high fault currents or DC offset components. This saturation causes the CT to become non-linear and unable to accurately reproduce the primary current on the secondary side. As a result, the secondary current is distorted, and the protection system might receive incorrect information.
In differential protection schemes, where the balance of currents between CTs is essential, CT saturation can lead to false tripping or failure to trip under actual fault conditions.
#### **How HIDP Handles CT Saturation**
HIDP deals with CT saturation in a very effective way, using several techniques:
1. **High Impedance Relay**:
- The core of the HIDP scheme is the high impedance relay. The relay has a high impedance input, meaning it will only operate if a significant voltage appears across its terminals.
- When all CTs are working correctly, the secondary currents are balanced, and there is minimal voltage across the relay. However, during a fault (and assuming proper CT operation), any differential current will produce enough voltage to operate the relay.
**How this helps with CT saturation**:
- When a CT saturates due to external faults (outside the protected zone), the distorted secondary current from the saturated CT could cause a false differential current. But since the secondary impedance of the HIDP circuit is designed to be high, the overall differential voltage remains below the relay's operating threshold. This means the relay won't operate for an external fault even if CTs saturate.
2. **Stabilizing Resistor**:
- A **stabilizing resistor** is used in series with the high impedance relay. This resistor ensures that during CT saturation (especially for external faults), the voltage across the relay does not exceed the operating threshold.
**How this helps**:
- When an external fault occurs and CTs saturate, the large fault current might cause a large differential current due to CT errors. However, the stabilizing resistor ensures that this differential current does not cause enough voltage across the relay to trip it. Essentially, the stabilizing resistor absorbs part of the voltage and keeps the relay from mis-operating.
3. **Voltage Setting Based on Worst-Case CT Saturation**:
- The HIDP scheme is designed with a voltage setting that is high enough to ignore CT errors but low enough to detect actual faults. This setting is chosen based on the **worst-case CT saturation** scenario.
**How this helps**:
- The relay is designed to have a pick-up voltage higher than the voltage that would be developed across the CT secondary during CT saturation for external faults. This way, the relay remains secure even if CTs saturate due to external disturbances.
4. **Non-Linear Resistors (Metrosils)**:
- **Metrosils** (or non-linear resistors) are used to protect the CT secondary circuit and the relay from overvoltage. During severe faults or CT saturation, very high voltages can develop across the relay. The Metrosils limit this voltage to a safe level by conducting at higher voltages.
**How this helps**:
- If a very high voltage appears due to CT saturation or during heavy internal faults, the Metrosil absorbs the excess voltage, preventing damage to the relay and the CT circuit.
5. **Protection Against External Faults**:
- In HIDP, the system is designed to distinguish between internal and external faults. During external faults, CT saturation is more likely, especially in the CT closest to the fault. However, since the CTs of the non-faulted side will still be producing accurate currents, the voltage developed across the differential relay remains below the operating threshold.
**How this helps**:
- HIDP uses its high impedance characteristics to block relay operation during external faults with CT saturation, maintaining security. In the case of an internal fault, even if some CTs saturate, the differential current is high enough to develop sufficient voltage to trip the relay.
#### **How HIDP Operates During an Internal Fault (with CT Saturation)**
When an internal fault occurs, the situation is different:
1. **Current Flow**: A large differential current flows through the CTs, and even if some CTs saturate, the unsaturated CTs will produce enough differential current.
2. **High Voltage Across Relay**: This results in a high voltage across the relay, which exceeds the voltage threshold and causes the relay to operate. Even with CT saturation, the differential current produced during an internal fault is large enough to trip the relay.
3. **Metrosils**: The metrosils protect the relay from overvoltage during such high fault conditions.
#### **Summary of Key Concepts**
1. **High Impedance Relay**: It only trips when a significant voltage (due to internal faults) develops across its terminals.
2. **Stabilizing Resistor**: Limits false trips during external faults with CT saturation.
3. **Metrosils**: Protects the relay from overvoltage due to high fault currents or CT saturation.
4. **Secure Operation**: HIDP is secure for external faults with CT saturation, but sensitive enough to trip for internal faults.
In essence, HIDP schemes handle CT saturation effectively by using high impedance, stabilizing resistors, metrosils, and voltage settings carefully designed to ignore errors from CT saturation while still detecting actual internal faults.