Define the following terms related to current interrupting devices: i) arc voltage, ii) re-striking voltage, iii) recovery voltage, iv) RRRV.

2 Answers

 
Best answer
Sure! These terms are crucial for understanding how current interrupting devices, such as circuit breakers and switches, function. Here's a detailed explanation of each term:

### i) Arc Voltage

**Arc Voltage** is the voltage that appears across the contacts of a circuit breaker or switch while it is interrupting the current. When a circuit breaker opens to interrupt the current, an electric arc forms between the separating contacts. The voltage across this arc is called the arc voltage. This voltage is generally higher than the normal operating voltage because the arc acts like a resistor, creating a voltage drop. The arc voltage needs to be managed effectively to ensure that the circuit breaker can safely interrupt the current without causing damage to the device or creating dangerous conditions.

### ii) Re-striking Voltage

**Re-striking Voltage** is the voltage that appears across the contacts of a circuit breaker immediately after the current has been interrupted and the arc has extinguished. This voltage is significant because, after the arc is extinguished, there can still be a transient voltage across the contacts due to the inductive elements in the circuit. The re-striking voltage can sometimes be high enough to cause the arc to re-ignite, which can lead to a phenomenon known as "re-striking" or "re-ignition" of the arc. Proper design and insulation are crucial to handle this voltage and prevent re-ignition.

### iii) Recovery Voltage

**Recovery Voltage** is the voltage that appears across the contacts of a circuit breaker after the arc has been extinguished and the contacts have separated. This is the voltage that the circuit breaker must withstand after interrupting the current. Recovery voltage is influenced by various factors including the system voltage, inductance of the circuit, and the residual voltage after the arc extinguishes. It's important for the circuit breaker to be able to withstand this recovery voltage to ensure it remains reliable and safe in subsequent operations.

### iv) RRRV (Rate of Rise of Recovery Voltage)

**RRRV (Rate of Rise of Recovery Voltage)** refers to the rate at which the recovery voltage increases after the current is interrupted. It is a measure of how quickly the voltage across the contacts of the circuit breaker increases after the arc is extinguished. The rate of rise can be influenced by the circuit's inductance and the characteristics of the current interrupting device. High RRRV can pose challenges for circuit breakers because it means the device must handle rapidly increasing voltages, which can stress the insulation and design of the device. Managing RRRV is critical for ensuring that circuit breakers can reliably interrupt and safely interrupt high currents.

In summary, these terms are related to the behavior of current interrupting devices during and after the interruption of electrical current. Proper understanding and management of arc voltage, re-striking voltage, recovery voltage, and RRRV are essential for designing reliable and safe electrical systems.
0 like 0 dislike
Current interrupting devices, such as circuit breakers, are critical components in electrical systems, ensuring safe and reliable operation by interrupting current flow under fault conditions. Below are the definitions of the terms related to these devices:

### I) Arc Voltage
**Arc voltage** is the voltage that appears across the contacts of a circuit breaker during the arcing period when the contacts begin to separate and before the arc is completely extinguished. When a circuit breaker interrupts a current, an electric arc is formed between the separating contacts due to the ionization of air or other insulating medium. The arc voltage is typically lower than the system voltage but persists as long as the arc exists. The arc voltage is a key factor because it influences the energy required to extinguish the arc and the ability of the circuit breaker to interrupt the current.

### II) Re-Striking Voltage
**Re-striking voltage** is the transient voltage that appears across the breaker contacts immediately after current interruption but before the dielectric strength of the medium between the contacts has fully recovered. This voltage can cause the arc to re-ignite or "restrike" if the dielectric strength of the medium between the contacts is insufficient to withstand the voltage. Re-striking voltage is a concern because it can lead to multiple re-ignitions of the arc, which can delay the final interruption of the current and possibly damage the circuit breaker.

### III) Recovery Voltage
**Recovery voltage** is the voltage that appears across the terminals of a circuit breaker after the arc has been extinguished and the contacts have separated completely, allowing the dielectric strength between the contacts to restore. It represents the system voltage or a portion of it that reappears across the circuit breaker terminals after successful interruption of the fault current. Recovery voltage is crucial for ensuring that the circuit breaker has successfully isolated the fault and that the system has returned to its normal operating state.

### IV) Rate of Rise of Restriking Voltage (RRRV)
**Rate of Rise of Restriking Voltage (RRRV)** is the rate at which the re-striking voltage increases across the breaker contacts immediately after the current is interrupted. RRRV is measured in volts per microsecond (V/µs) and is an important factor in the design of circuit breakers. A high RRRV can challenge the dielectric recovery of the medium between the contacts and can increase the likelihood of a restrike occurring. Circuit breakers must be designed to handle specific RRRV levels to ensure they can successfully interrupt current without restriking.

In summary, these terms relate to the dynamics of voltage across circuit breaker contacts during the interruption process. Proper understanding and control of these voltages are essential for the reliable operation of circuit breakers in electrical power systems.
0 like 0 dislike

Related questions

Define the following terms related to circuit breaker: i) Breaking Capacity ii) Making Capacity iii) Short time rating iv) Normal current rating.
Answer : Sure! To better assist you, could you specify if you’re looking for definitions in a particular context, such as residential, industrial, or another area?...

Show More

Define the following terms related to CB: i) Rated normal current ii) Rated breaking current iii) Short time rating iv) Symmetrical breaking current.
Answer : Certainly! Let's define these key terms related to circuit breakers (CB) in detail. ### i) Rated Normal Current **Definition:** Rated normal current (often referred to ... and applying circuit breakers in electrical systems, ensuring safety, reliability, and compliance with electrical standards....

Show More

Define the following terms related to logic families: (i) Noise Margin (ii) FAN-OUT (iii) Propagation delay (iv) Power dissipation.
Answer : Sure! Let's break down these terms related to logic families in detail: ### (i) Noise Margin **Noise Margin** is a measure of a circuit's ability to withstand noise without ... They help ensure reliability, performance, and efficiency in digital systems, which are critical for modern electronics....

Show More

Define the following terms with respect to protective relays: i) Relay time ii) Reset current iii) Plug setting multiplier iv) Time setting multiplier.
Answer : Protective relays are crucial in electrical systems for detecting faults and initiating protective actions. Here's a detailed definition of the terms you asked about: ### i) Relay ... systems to provide effective fault detection and isolation, ultimately enhancing system reliability and safety....

Show More

Define the following terms: (i) Average demand (ii) Load factor (iii) Plant capacity factor (iv) Plant use factor
Answer : Sure, I'll provide detailed explanations for each term: ### (i) Average Demand **Average Demand** refers to the average amount of electrical power or energy required over a specific period. It ... potential. - **Plant Use Factor** measures how much of the installed capacity is actually used....

Show More
Welcome to Electrical Engineering, where you can ask questions and receive answers from other members of the community.