πŸ”
A 3 phase line of 4 km length delivers 4000 kW at a p.f of 0.8 lagging to a load the resistance and reactance per km of each conductor are 0.2 Ω and 0.5 Ω respectively if the voltage at the supply end is maintained at 11 kV. Calculate the received end voltage and efficiency of line.

2 Answers

 
️
Best answer
To calculate the **received end voltage** and the **efficiency** of the transmission line, we need to follow these steps:

### 1. **Given data:**
- Load power (\( P_L \)) = 4000 kW = 4000 Γ— 10Β³ W
- Power factor (p.f.) = 0.8 lagging
- Load voltage at the sending end (\( V_s \)) = 11 kV = 11 Γ— 10Β³ V
- Line length (\( l \)) = 4 km
- Resistance per km (\( R \)) = 0.2 Ω/km
- Reactance per km (\( X \)) = 0.5 Ω/km

### 2. **Calculate total line impedance:**
For a 3-phase line, the total resistance and reactance are calculated by multiplying the per km values by the line length:

- Total resistance (\( R_{\text{total}} \)) = \( R \times l = 0.2 \times 4 = 0.8 \, \Omega \)
- Total reactance (\( X_{\text{total}} \)) = \( X \times l = 0.5 \times 4 = 2.0 \, \Omega \)

Thus, the total impedance (\( Z_{\text{total}} \)) of the line is:
\[
Z_{\text{total}} = R_{\text{total}} + jX_{\text{total}} = 0.8 + j2.0 \, \Omega
\]

### 3. **Calculate the load current:**

First, calculate the apparent power \( S_L \) delivered to the load:
\[
S_L = \frac{P_L}{\text{p.f.}} = \frac{4000 \, \text{kW}}{0.8} = 5000 \, \text{kVA}
\]

The load current for a 3-phase system is:
\[
I_L = \frac{S_L}{\sqrt{3} \times V_r} = \frac{5000 \times 10^3}{\sqrt{3} \times V_r}
\]
Where \( V_r \) is the received end voltage (unknown at this point). Since we don't yet have \( V_r \), we'll approximate it using the sending end voltage \( V_s \).

Let’s assume \( V_r \approx V_s = 11 \, \text{kV} \) for now to estimate \( I_L \):

\[
I_L = \frac{5000 \times 10^3}{\sqrt{3} \times 11 \times 10^3} = \frac{5000}{\sqrt{3} \times 11} = 262.43 \, \text{A}
\]

### 4. **Calculate voltage drop across the line:**

The voltage drop across the transmission line is:
\[
\Delta V = I_L \times Z_{\text{total}}
\]
Using the impedance (\( Z_{\text{total}} = 0.8 + j2.0 \)):

\[
\Delta V = 262.43 \times (0.8 + j2.0) = 262.43 \times 0.8 + j262.43 \times 2.0 = 209.94 + j524.86 \, \text{V}
\]

Now, calculate the magnitude of this voltage drop:
\[
|\Delta V| = \sqrt{209.94^2 + 524.86^2} = \sqrt{44067.1 + 275476.9} = \sqrt{319544} = 565.15 \, \text{V}
\]

### 5. **Calculate the received end voltage:**

The sending end voltage is 11 kV, and the voltage drop across the line is \( \Delta V \). The received end voltage \( V_r \) is the difference between the sending end voltage and the voltage drop:

For a 3-phase system, we must convert the line voltage to the phase voltage. The phase voltage for the sending end is:
\[
V_s^{\text{phase}} = \frac{V_s}{\sqrt{3}} = \frac{11 \times 10^3}{\sqrt{3}} = 6350.85 \, \text{V}
\]

Subtracting the voltage drop:
\[
V_r^{\text{phase}} = V_s^{\text{phase}} - |\Delta V| = 6350.85 - 565.15 = 5785.7 \, \text{V}
\]

Now, convert the received phase voltage back to the line voltage:
\[
V_r = V_r^{\text{phase}} \times \sqrt{3} = 5785.7 \times \sqrt{3} = 10020 \, \text{V} = 10.02 \, \text{kV}
\]

### 6. **Calculate the efficiency of the line:**

The efficiency \( \eta \) is given by:
\[
\eta = \frac{P_r}{P_s} \times 100\%
\]
Where \( P_s \) is the sending end power, and \( P_r = P_L = 4000 \, \text{kW} \).

The sending end power \( P_s \) can be approximated as:
\[
P_s = \sqrt{3} \times V_s \times I_L \times \text{p.f.}
\]
Substitute the values:
\[
P_s = \sqrt{3} \times 11 \times 262.43 \times 0.8 = 4009.75 \, \text{kW}
\]

Finally, the efficiency is:
\[
\eta = \frac{4000}{4009.75} \times 100\% = 99.76\%
\]

### **Final Results:**
- **Received end voltage**: \( V_r \approx 10.02 \, \text{kV} \)
- **Efficiency of the line**: \( \eta \approx 99.76\% \)
0 like 0 dislike
To solve this problem, we need to calculate the received end voltage and the efficiency of the 3-phase transmission line. We'll proceed through the following steps:

### Given Data:
- Length of the line \( L = 4 \) km
- Power delivered \( P = 4000 \) kW
- Power factor \( \text{pf} = 0.8 \) (lagging)
- Resistance per km \( R = 0.2 \, \Omega/\text{km} \)
- Reactance per km \( X = 0.5 \, \Omega/\text{km} \)
- Voltage at the supply end \( V_s = 11 \text{ kV} \) (line-to-line)

### Step 1: Calculate the Total Line Resistance and Reactance

1. **Total Line Resistance \( R_{total} \):**
   \[
   R_{total} = R \times L = 0.2 \, \Omega/\text{km} \times 4 \text{ km} = 0.8 \, \Omega
   \]

2. **Total Line Reactance \( X_{total} \):**
   \[
   X_{total} = X \times L = 0.5 \, \Omega/\text{km} \times 4 \text{ km} = 2.0 \, \Omega
   \]

### Step 2: Calculate the Load Current

1. **Calculate the load power in kVA:**
   \[
   S = \frac{P}{\text{pf}} = \frac{4000 \text{ kW}}{0.8} = 5000 \text{ kVA}
   \]

2. **Calculate the load current (line-to-line voltage):**

   First, find the line-to-neutral voltage \( V_{LN} \) at the supply end:
   \[
   V_{LN} = \frac{V_s}{\sqrt{3}} = \frac{11 \text{ kV}}{\sqrt{3}} \approx 6.35 \text{ kV}
   \]

   Then, calculate the load current \( I_L \):
   \[
   I_L = \frac{S}{\sqrt{3} \times V_{LN}} = \frac{5000 \text{ kVA}}{\sqrt{3} \times 6.35 \text{ kV}} \approx \frac{5000 \text{ kVA}}{11 \text{ kV}} \approx 454.5 \text{ A}
   \]

### Step 3: Calculate the Voltage Drop Across the Line

1. **Voltage drop in each phase:**
   \[
   V_{drop} = I_L \times (R_{total} + jX_{total})
   \]

   Substitute the values:
   \[
   V_{drop} = 454.5 \text{ A} \times (0.8 \, \Omega + j2.0 \, \Omega)
   \]

2. **Calculate the magnitude of the voltage drop:**
   \[
   |V_{drop}| = 454.5 \times \sqrt{0.8^2 + 2.0^2} = 454.5 \times \sqrt{0.64 + 4.0} = 454.5 \times \sqrt{4.64} \approx 454.5 \times 2.15 \approx 977.2 \text{ V}
   \]

### Step 4: Calculate the Received End Voltage

1. **Received end voltage \( V_R \):**
   \[
   V_R = V_s - V_{drop}
   \]

   Convert \( V_{drop} \) to line-to-line voltage:
   \[
   V_{drop} \text{ (line-to-line)} = |V_{drop}| \times \sqrt{3} = 977.2 \text{ V} \times \sqrt{3} \approx 1690 \text{ V}
   \]

   Finally, calculate \( V_R \):
   \[
   V_R = 11 \text{ kV} - 1.69 \text{ kV} = 9.31 \text{ kV}
   \]

### Step 5: Calculate the Efficiency of the Line

1. **Calculate the input power \( P_{in} \):**
   \[
   P_{in} = \sqrt{3} \times V_s \times I_L \times \text{pf}
   \]

   Substitute values:
   \[
   P_{in} = \sqrt{3} \times 11 \text{ kV} \times 454.5 \text{ A} \times 0.8 \approx \sqrt{3} \times 11 \times 454.5 \times 0.8 \approx 11 \times 454.5 \times 1.38 \approx 6926 \text{ kW}
   \]

2. **Calculate the efficiency:**
   \[
   \text{Efficiency} = \frac{P_{out}}{P_{in}} \times 100\% = \frac{4000 \text{ kW}}{6926 \text{ kW}} \times 100\% \approx 57.8\%
   \]

### Summary

- **Received End Voltage**: Approximately \( 9.31 \text{ kV} \)
- **Efficiency of the Line**: Approximately \( 57.8\% \)
0 like 0 dislike

Related questions

A 250/125 V, 5 KVA single-phase transformer has primary resistance of 0.2 Ω and reactance of 0.75 Ω. The secondary resistance is 0.05 Ω and reactance of 0.2 Ω. Determine its regulation while supplying full load on 0.8 leading P.F.
Answer : To calculate the voltage regulation of a transformer, we use the formula: \[ \text{Voltage Regulation} = \frac{V_{nl} - V_{fl}}{V_{fl}} \times 100 \] Where: - \( V_{nl} ... is approximately **-4.88%**. The negative sign indicates that the voltage rises under leading power factor conditions....

Show More

A 3 phase, 50 Hz 8 pole induction motor has full load slip of 2%. The rotor resistance and standstill rotor reactance per phase are 0.001 ohm and 0.005 ohm respectively. Find the ratio of maximum to full load torque and the speed at which the maximum torque occurs.
Answer : To solve this problem, we'll use the given data to calculate the ratio of maximum to full load torque and the speed at which the maximum torque occurs. Here's the step-by-step ... applied, and cross-check if the actual motor design has any additional factors affecting the torque characteristics....

Show More

A 20 KVA, 2200/220V, 50 Hz transformer has O.C/S.C test results as follows: O.C.test : 220V, 4.2 A, 148 W (l. v. side), S.C. test : 86V, 10.5 A, 360 W (h. v. side). Determine the regulation at 0.8 P.F lagging at full load.
Answer : To determine the voltage regulation at 0.8 power factor lagging for the transformer, we first need to calculate the full-load current on the low voltage (LV) side, then find the equivalent reactance and ... the ultimate regulation at 0.8 power factor lagging at full load is approximately **304.8%**....

Show More

A 500 KVA, 3-phase, 50 Hz transformer has a voltage ratio (line voltages) of 33/11KV and is delta/star connected. The resistance per phase is: high voltage 35 Ω low voltage 0.876 Ω and iron loss is 3050W. Calculate the value of efficiency at full load.
Answer : To calculate the efficiency of the transformer at full load, we will follow these steps: 1. **Determine the full load current on both sides of the transformer.** 2. **Calculate the ... *98.91%**. This indicates that the transformer is quite efficient in transferring power with minimal losses....

Show More

Find the all-day efficiency of a 500 KVA distribution transformer whose copper loss and iron loss at full load are 4.5 KW and 3.5 KW respectively. During a day of 24 hours, it is loaded as under: No of hours Loading in KW Power factor 6 400 0.8 10 300 0.75 4 100 0.8 4 0 -.
Answer : To find the all-day efficiency of a distribution transformer, we'll follow these steps: 1. **Calculate the Total Energy Input to the Transformer:** The energy input to the transformer ... Conclusion The all-day efficiency of the 500 KVA distribution transformer is approximately **97.55%**....

Show More
Welcome to Electrical Engineering, where you can ask questions and receive answers from other members of the community.