🔍
A 20 KVA, 2200/220V, 50 Hz transformer has O.C/S.C test results as follows: O.C.test : 220V, 4.2 A, 148 W (l. v. side), S.C. test : 86V, 10.5 A, 360 W (h. v. side). Determine the regulation at 0.8 P.F lagging at full load.

2 Answers

 
Best answer
To determine the voltage regulation at 0.8 power factor lagging for the transformer, we first need to calculate the full-load current on the low voltage (LV) side, then find the equivalent reactance and resistance from the tests.

1. **Full-load Current (I_FL)**:
   \[
   I_{FL} = \frac{20,000 \text{ VA}}{220 \text{ V}} = 90.91 \text{ A}
   \]

2. **From O.C. Test**:
   \[
   V_{oc} = 220 \text{ V}, \quad I_{oc} = 4.2 \text{ A}, \quad P_{oc} = 148 \text{ W}
   \]
   \[
   R_{oc} = \frac{P_{oc}}{I_{oc}^2} = \frac{148}{(4.2)^2} \approx 8.45 \Omega
   \]
   \[
   Z_{oc} = \frac{V_{oc}}{I_{oc}} = \frac{220}{4.2} \approx 52.38 \Omega
   \]
   \[
   X_{oc} = \sqrt{Z_{oc}^2 - R_{oc}^2} \approx \sqrt{52.38^2 - 8.45^2} \approx 52.25 \Omega
   \]

3. **From S.C. Test**:
   \[
   V_{sc} = 86 \text{ V}, \quad I_{sc} = 10.5 \text{ A}, \quad P_{sc} = 360 \text{ W}
   \]
   \[
   R_{sc} = \frac{P_{sc}}{I_{sc}^2} = \frac{360}{(10.5)^2} \approx 3.27 \Omega
   \]
   \[
   Z_{sc} = \frac{V_{sc}}{I_{sc}} = \frac{86}{10.5} \approx 8.19 \Omega
   \]
   \[
   X_{sc} = \sqrt{Z_{sc}^2 - R_{sc}^2} \approx \sqrt{8.19^2 - 3.27^2} \approx 7.94 \Omega
   \]

4. **Equivalent Circuit Parameters**:
   \[
   R_{eq} \approx R_{sc} = 3.27 \Omega, \quad X_{eq} \approx X_{sc} = 7.94 \Omega
   \]

5. **Voltage Drop (V_drop)**:
   \[
   I_{FL} = 90.91 \text{ A}, \quad \text{at } 0.8 \text{ P.F.}:
   \]
   \[
   V_{drop} = I_{FL} \times (R_{eq} \cos \phi + X_{eq} \sin \phi)
   \]
   Where \(\cos \phi = 0.8\) and \(\sin \phi = \sqrt{1 - (0.8)^2} \approx 0.6\):
   \[
   V_{drop} = 90.91 \times (3.27 \times 0.8 + 7.94 \times 0.6) \approx 90.91 \times (2.616 + 4.764) \approx 90.91 \times 7.38 \approx 670.61 \text{ V}
   \]

6. **Voltage Regulation**:
   \[
   V_{reg} = \frac{V_{drop}}{V_{FL}} \times 100 = \frac{670.61}{220} \times 100 \approx 304.8\%
   \]

Thus, the ultimate regulation at 0.8 power factor lagging at full load is approximately **304.8%**.
0 like 0 dislike
To determine the voltage regulation of the transformer at 0.8 power factor (p.f.) lagging and full load, follow these steps:

### Given Data:
- **Transformer Rating:** 20 kVA
- **Primary (High Voltage, HV) Voltage:** 2200 V
- **Secondary (Low Voltage, LV) Voltage:** 220 V
- **Frequency:** 50 Hz

**Open Circuit (O.C.) Test Results:**
- **Voltage:** 220 V
- **Current:** 4.2 A
- **Power:** 148 W

**Short Circuit (S.C.) Test Results:**
- **Voltage:** 86 V
- **Current:** 10.5 A
- **Power:** 360 W

### 1. Calculate the Transformer Impedance and Parameters

#### a. **O.C. Test Analysis:**

The open-circuit test is performed on the low-voltage (LV) side, so we determine the core loss (or no-load loss) and the no-load current:

- **Core Loss (P_core):** 148 W
- **No-load Current (I_0):** 4.2 A
- **No-load Voltage (V_0):** 220 V

The core loss corresponds to the constant loss in the transformer due to the magnetizing current.

#### b. **S.C. Test Analysis:**

The short-circuit test is performed on the HV side, so we determine the copper loss (or short-circuit loss) and the short-circuit impedance:

- **Short-Circuit Loss (P_sc):** 360 W
- **Short-Circuit Voltage (V_sc):** 86 V
- **Short-Circuit Current (I_sc):** 10.5 A

The short-circuit impedance can be calculated as:
\[ Z_{sc} = \frac{V_{sc}}{I_{sc}} = \frac{86 \text{ V}}{10.5 \text{ A}} = 8.19 \text{ ohms} \]

### 2. Determine the Equivalent Circuit Parameters

From the short-circuit test, the impedance and the copper loss are known. We can use these to determine the resistance and reactance:

**Copper Loss (P_cu):** 360 W

The copper loss is given by:
\[ P_{cu} = I_{sc}^2 \times R_{sc} \]

Rearrange to find \( R_{sc} \):
\[ R_{sc} = \frac{P_{cu}}{I_{sc}^2} = \frac{360 \text{ W}}{(10.5 \text{ A})^2} = 3.24 \text{ ohms} \]

The reactance can be calculated using:
\[ X_{sc} = \sqrt{Z_{sc}^2 - R_{sc}^2} = \sqrt{(8.19 \text{ ohms})^2 - (3.24 \text{ ohms})^2} = 7.05 \text{ ohms} \]

### 3. Calculate the Voltage Regulation

The voltage regulation is given by:
\[ \text{Regulation} = \frac{V_{no-load} - V_{full-load}}{V_{full-load}} \times 100\% \]

**Step 1: Determine Full-Load Secondary Voltage**

At full load, the voltage drop across the impedance due to the load current needs to be considered. We need to find the full-load voltage drop in the secondary winding.

The full-load current on the secondary side is:
\[ I_{FL} = \frac{20 \text{ kVA}}{220 \text{ V}} = 90.91 \text{ A} \]

**Step 2: Convert Secondary Impedance to Primary Side**

The impedance on the secondary side is transformed to the primary side using the turns ratio squared:
\[ Z_{sec} = \left(\frac{2200}{220}\right)^2 \times Z_{sc} = 100 \times 8.19 \text{ ohms} = 819 \text{ ohms} \]

**Step 3: Calculate the Voltage Drop**

The full-load voltage drop on the primary side is:
\[ V_{drop} = I_{FL} \times Z_{sc} \]

However, to determine the voltage regulation, the voltage drop needs to be converted to the secondary side. Given the turns ratio is 10 (2200/220):
\[ V_{drop} = \frac{360 \text{ W}}{10.5 \text{ A}} = 34.29 \text{ V} \text{ (on secondary side)} \]

### Final Calculation

**Voltage Regulation:**

\[ \text{Regulation} = \frac{V_{no-load} - V_{full-load}}{V_{full-load}} \times 100\% \]

Assuming the no-load voltage \( V_{no-load} \) is \( 220 \text{ V} \) and the full-load voltage \( V_{full-load} = 220 - 34.29 = 185.71 \text{ V} \):

\[ \text{Regulation} = \frac{220 - 185.71}{185.71} \times 100\% \approx 18.6\% \]

Thus, the voltage regulation of the transformer at 0.8 p.f. lagging and full load is approximately **18.6%**.
0 like 0 dislike

Related questions

A 250/125 V, 5 KVA single-phase transformer has primary resistance of 0.2 Ω and reactance of 0.75 Ω. The secondary resistance is 0.05 Ω and reactance of 0.2 Ω. Determine its regulation while supplying full load on 0.8 leading P.F.
Answer : To calculate the voltage regulation of a transformer, we use the formula: \[ \text{Voltage Regulation} = \frac{V_{nl} - V_{fl}}{V_{fl}} \times 100 \] Where: - \( V_{nl} ... is approximately **-4.88%**. The negative sign indicates that the voltage rises under leading power factor conditions....

Show More

A 20 pole, 693V, 50 Hz, 3 phase, delta connected synchronous motor is operating at no load with normal excitation. It has armature resistance per phase of zero and synchronous reactance of 10 ohm. If ... iii) armature current /phase, iv) power drawn by the motor and v) power developed by armature.
Answer : To solve the problem, let's break it down step by step: ### Given Data - **Number of poles (P)**: 20 - **Voltage (V)**: 693V (line-to-line) - **Frequency (f)**: 50 Hz - ** ... **Power drawn by the motor**: Approximately 4,188 W - **Power developed by the armature**: Approximately 407.6 W...

Show More

A 3 phase line of 4 km length delivers 4000 kW at a p.f of 0.8 lagging to a load the resistance and reactance per km of each conductor are 0.2 Ω and 0.5 Ω respectively if the voltage at the supply end is maintained at 11 kV. Calculate the received end voltage and efficiency of line.
Answer : To calculate the **received end voltage** and the **efficiency** of the transmission line, we need to follow these steps: ### 1. **Given data:** - Load power (\( P_L \)) = 4000 kW = 4000 10³ W - Power factor ... approx 10.02 \, \text{kV} \) - **Efficiency of the line**: \( \eta \approx 99.76\% \)...

Show More

Find the all-day efficiency of a 500 KVA distribution transformer whose copper loss and iron loss at full load are 4.5 KW and 3.5 KW respectively. During a day of 24 hours, it is loaded as under: No of hours Loading in KW Power factor 6 400 0.8 10 300 0.75 4 100 0.8 4 0 -.
Answer : To find the all-day efficiency of a distribution transformer, we'll follow these steps: 1. **Calculate the Total Energy Input to the Transformer:** The energy input to the transformer ... Conclusion The all-day efficiency of the 500 KVA distribution transformer is approximately **97.55%**....

Show More

A 500 KVA, 3-phase, 50 Hz transformer has a voltage ratio (line voltages) of 33/11KV and is delta/star connected. The resistance per phase is: high voltage 35 Ω low voltage 0.876 Ω and iron loss is 3050W. Calculate the value of efficiency at full load.
Answer : To calculate the efficiency of the transformer at full load, we will follow these steps: 1. **Determine the full load current on both sides of the transformer.** 2. **Calculate the ... *98.91%**. This indicates that the transformer is quite efficient in transferring power with minimal losses....

Show More
Welcome to Electrical Engineering, where you can ask questions and receive answers from other members of the community.