🔍
A 250/125 V, 5 KVA single-phase transformer has primary resistance of 0.2 Ω and reactance of 0.75 Ω. The secondary resistance is 0.05 Ω and reactance of 0.2 Ω. Determine its regulation while supplying full load on 0.8 leading P.F.

2 Answers

 
Best answer
To calculate the voltage regulation of a transformer, we use the formula:

\[
\text{Voltage Regulation} = \frac{V_{nl} - V_{fl}}{V_{fl}} \times 100
\]

Where:
- \( V_{nl} \) is the no-load voltage (voltage at open circuit)
- \( V_{fl} \) is the full-load voltage

However, the above formula requires the full-load and no-load voltages, which can be derived from the impedance of the transformer and the power factor. Since you're given the resistances, reactances, and the power factor, we can use an alternative method to calculate the voltage regulation.

### Given:
- Primary Voltage (\( V_1 \)) = 250 V
- Secondary Voltage (\( V_2 \)) = 125 V
- Apparent Power \( S = 5 \, \text{kVA} \)
- Primary Resistance (\( R_1 \)) = 0.2 Ω
- Primary Reactance (\( X_1 \)) = 0.75 Ω
- Secondary Resistance (\( R_2 \)) = 0.05 Ω
- Secondary Reactance (\( X_2 \)) = 0.2 Ω
- Power Factor = 0.8 (leading)

### Step 1: Calculate the equivalent impedance referred to the primary side

The secondary resistances and reactances are referred to the primary side using the turns ratio \( a \), which is given by:

\[
a = \frac{V_1}{V_2} = \frac{250}{125} = 2
\]

Now, refer the secondary resistances and reactances to the primary side:

- Referred secondary resistance: \( R_2' = R_2 \times a^2 = 0.05 \times 2^2 = 0.2 \, \Omega \)
- Referred secondary reactance: \( X_2' = X_2 \times a^2 = 0.2 \times 2^2 = 0.8 \, \Omega \)

### Step 2: Calculate total equivalent impedance on the primary side

Now, add the referred values to the primary resistances and reactances:

\[
R_{eq} = R_1 + R_2' = 0.2 + 0.2 = 0.4 \, \Omega
\]
\[
X_{eq} = X_1 + X_2' = 0.75 + 0.8 = 1.55 \, \Omega
\]

### Step 3: Calculate the impedance magnitude

The equivalent impedance magnitude is:

\[
Z_{eq} = \sqrt{R_{eq}^2 + X_{eq}^2} = \sqrt{0.4^2 + 1.55^2} = \sqrt{0.16 + 2.4025} = \sqrt{2.5625} = 1.6 \, \Omega
\]

### Step 4: Full-load current

The full-load current on the primary side is given by:

\[
I_{fl} = \frac{S}{V_1} = \frac{5000}{250} = 20 \, \text{A}
\]

### Step 5: Voltage drop across the equivalent impedance

The voltage drop across the equivalent impedance is:

\[
V_{drop} = I_{fl} \times Z_{eq} = 20 \times 1.6 = 32 \, \text{V}
\]

### Step 6: Effect of power factor

Since the power factor is leading (0.8 leading), the voltage drop is not entirely resistive, so we need to decompose it into real and imaginary components:

- Real component (resistive drop): \( I_{fl} R_{eq} = 20 \times 0.4 = 8 \, \text{V} \)
- Imaginary component (reactive drop): \( I_{fl} X_{eq} = 20 \times 1.55 = 31 \, \text{V} \)

For a leading power factor, the voltage drop due to reactance is subtracted. So the net voltage drop:

\[
V_{net} = (I_{fl} R_{eq}) \cos(\theta) - (I_{fl} X_{eq}) \sin(\theta)
\]

Where:
- \( \cos(\theta) = 0.8 \) (power factor)
- \( \sin(\theta) = 0.6 \) (from \( \sin(\theta) = \sqrt{1 - \cos^2(\theta)} \))

\[
V_{net} = 8 \times 0.8 - 31 \times 0.6 = 6.4 - 18.6 = -12.2 \, \text{V}
\]

### Step 7: Voltage regulation

Finally, the voltage regulation is:

\[
\text{Voltage Regulation} = \frac{V_{net}}{V_1} \times 100 = \frac{-12.2}{250} \times 100 = -4.88\%
\]

### Conclusion:

The voltage regulation of the transformer at full load with a power factor of 0.8 leading is approximately **-4.88%**. The negative sign indicates that the voltage rises under leading power factor conditions.
0 like 0 dislike
To determine the voltage regulation of the transformer under full load with a power factor of 0.8 leading, we'll follow these steps:

1. **Given Data:**
   - Primary Voltage \( V_1 = 250 \, V \)
   - Secondary Voltage \( V_2 = 125 \, V \)
   - Apparent Power \( S = 5 \, kVA = 5000 \, VA \)
   - Primary Resistance \( R_1 = 0.2 \, \Omega \)
   - Primary Reactance \( X_1 = 0.75 \, \Omega \)
   - Secondary Resistance \( R_2 = 0.05 \, \Omega \)
   - Secondary Reactance \( X_2 = 0.2 \, \Omega \)
   - Power Factor \( \cos \phi = 0.8 \) (leading)

2. **Full Load Current Calculation:**
   \[
   I_2 = \frac{S}{V_2} = \frac{5000}{125} = 40 \, A
   \]

3. **Referred Impedance to Secondary Side:**
   Referred primary resistance and reactance to the secondary side:
   \[
   R_1' = \left(\frac{V_2}{V_1}\right)^2 R_1 = \left(\frac{125}{250}\right)^2 \times 0.2 \, \Omega = 0.05 \, \Omega
   \]
   \[
   X_1' = \left(\frac{V_2}{V_1}\right)^2 X_1 = \left(\frac{125}{250}\right)^2 \times 0.75 \, \Omega = 0.1875 \, \Omega
   \]

   Total resistance and reactance referred to the secondary side:
   \[
   R_{eq} = R_2 + R_1' = 0.05 + 0.05 = 0.1 \, \Omega
   \]
   \[
   X_{eq} = X_2 + X_1' = 0.2 + 0.1875 = 0.3875 \, \Omega
   \]

4. **Voltage Drop Calculation:**
   The voltage drop across the equivalent impedance:
   \[
   V_{drop} = I_2 \times (R_{eq} \cos \phi + X_{eq} \sin \phi)
   \]

   With \( \cos \phi = 0.8 \) and \( \sin \phi = 0.6 \) (for leading P.F.):
   \[
   V_{drop} = 40 \times (0.1 \times 0.8 - 0.3875 \times 0.6)
   \]
   \[
   V_{drop} = 40 \times (0.08 - 0.2325)
   \]
   \[
   V_{drop} = 40 \times (-0.1525) = -6.1 \, V
   \]

5. **Voltage Regulation Calculation:**
   Voltage regulation is given by:
   \[
   \text{Regulation} = \frac{V_{drop}}{V_2} \times 100\%
   \]
   \[
   \text{Regulation} = \frac{-6.1}{125} \times 100\% = -4.88\%
   \]

### Final Answer:
The voltage regulation of the transformer while supplying full load at a 0.8 leading power factor is \(-4.88\%\). This negative value indicates that the output voltage increases when the transformer is loaded, which is typical for a leading power factor.
0 like 0 dislike

Related questions

A 20 KVA, 2200/220V, 50 Hz transformer has O.C/S.C test results as follows: O.C.test : 220V, 4.2 A, 148 W (l. v. side), S.C. test : 86V, 10.5 A, 360 W (h. v. side). Determine the regulation at 0.8 P.F lagging at full load.
Answer : To determine the voltage regulation at 0.8 power factor lagging for the transformer, we first need to calculate the full-load current on the low voltage (LV) side, then find the equivalent reactance and ... the ultimate regulation at 0.8 power factor lagging at full load is approximately **304.8%**....

Show More

Define voltage regulation of alternator. A 400V, 10 KVA, 3 phase star connected alternator has resistance per phase of 1.0 ohm. Open circuit voltage per phase of 90V is obtained for field current of 1.0 ... per phase and iv) Regulation while supplying a load current of 15A at 0.8 power factor lag.
Answer : **Voltage Regulation of Alternator:** Voltage regulation of an alternator refers to the change in terminal voltage when the alternator shifts from no-load to full-load conditions while the field current remains constant. It' ... (\( E_{oc} \))**: 90 V 4. **Voltage Regulation**: Approximately 264.9%...

Show More

A 3 phase line of 4 km length delivers 4000 kW at a p.f of 0.8 lagging to a load the resistance and reactance per km of each conductor are 0.2 Ω and 0.5 Ω respectively if the voltage at the supply end is maintained at 11 kV. Calculate the received end voltage and efficiency of line.
Answer : To calculate the **received end voltage** and the **efficiency** of the transmission line, we need to follow these steps: ### 1. **Given data:** - Load power (\( P_L \)) = 4000 kW = 4000 10³ W - Power factor ... approx 10.02 \, \text{kV} \) - **Efficiency of the line**: \( \eta \approx 99.76\% \)...

Show More

For the tariff of 125/kVA of maximum demand and 3.00 per unit consumed; load factor = 50%, find overall cost/unit at i) unity power factor ii) 0.8 p.f consider maximum demand = 10 kVA.
Answer : To calculate the overall cost per unit (kWh) for the given tariff structure, we need to use the following steps: ### Given Data: - **Tariff for maximum demand**: ₹125 per kVA of maximum demand - **Tariff per unit consumed ... = **₹3.35** 2. **At power factor 0.8**: Overall cost per unit = **₹3.43**...

Show More

A 20 pole, 693V, 50 Hz, 3 phase, delta connected synchronous motor is operating at no load with normal excitation. It has armature resistance per phase of zero and synchronous reactance of 10 ohm. If ... iii) armature current /phase, iv) power drawn by the motor and v) power developed by armature.
Answer : To solve the problem, let's break it down step by step: ### Given Data - **Number of poles (P)**: 20 - **Voltage (V)**: 693V (line-to-line) - **Frequency (f)**: 50 Hz - ** ... **Power drawn by the motor**: Approximately 4,188 W - **Power developed by the armature**: Approximately 407.6 W...

Show More
Welcome to Electrical Engineering, where you can ask questions and receive answers from other members of the community.