🔍
How to calculate capacitor bank value to maintain unity power factor with some suitable example?

2 Answers

 
Best answer
To calculate the value of a capacitor bank needed to maintain a unity power factor, you need to understand the existing power factor of the system and how much reactive power compensation is required to bring it to unity (1.0). Here's a detailed step-by-step guide with an example:

### 1. **Understand the System's Power Factor**

First, you need to know the power factor of your system and the amount of real power (P) being used. Power factor (PF) is the ratio of real power (P) to apparent power (S). It can be expressed as:

\[ \text{Power Factor} = \frac{P}{S} \]

where:
- \( P \) is the real power in watts (W).
- \( S \) is the apparent power in volt-amperes (VA).

### 2. **Determine the Reactive Power Required**

The goal is to correct the power factor to unity (1.0). To achieve this, you need to add capacitors to supply the required reactive power (Q_c) to counteract the reactive power (Q) that is currently present.

The reactive power needed for power factor correction can be calculated using the following steps:

1. **Calculate the Current Reactive Power (Q):**
   \[ Q = S \cdot \sin(\theta) \]
   where \( \theta \) is the phase angle of the current power factor, given by:
   \[ \cos(\theta) = \text{Existing Power Factor} \]
   \[ \theta = \cos^{-1}(\text{Existing Power Factor}) \]
   \[ \sin(\theta) = \sqrt{1 - \cos^2(\theta)} \]

2. **Determine the Required Reactive Power (Q_c) for Unity Power Factor:**
   If the desired power factor is unity (1.0), then the total reactive power (Q_total) needs to be zero. Hence, the reactive power required by the capacitor bank (Q_c) is equal to the current reactive power (Q).

### 3. **Calculate the Capacitor Bank Value**

Capacitors provide reactive power in the form of capacitance. The reactive power provided by a capacitor is given by:

\[ Q_c = \frac{V^2}{X_c} \]

where:
- \( V \) is the voltage in volts (V).
- \( X_c \) is the capacitive reactance in ohms (Ω), which can be found using:
  \[ X_c = \frac{1}{2 \pi f C} \]
  where \( f \) is the frequency in hertz (Hz) and \( C \) is the capacitance in farads (F).

Rearranging for \( C \), you get:

\[ C = \frac{1}{2 \pi f X_c} \]
\[ X_c = \frac{V^2}{Q_c} \]

So:

\[ C = \frac{Q_c}{2 \pi f V^2} \]

### Example Calculation

Let's say you have a system with the following characteristics:
- **Real Power (P):** 100 kW
- **Existing Power Factor:** 0.8
- **System Voltage:** 400 V
- **Frequency:** 50 Hz

**Step 1: Calculate Apparent Power (S)**

\[ S = \frac{P}{\text{Power Factor}} = \frac{100,000}{0.8} = 125,000 \text{ VA} \]

**Step 2: Calculate Current Reactive Power (Q)**

\[ \cos(\theta) = 0.8 \]
\[ \theta = \cos^{-1}(0.8) \approx 36.87^\circ \]
\[ \sin(\theta) = \sqrt{1 - 0.8^2} = \sqrt{0.36} = 0.6 \]
\[ Q = S \cdot \sin(\theta) = 125,000 \cdot 0.6 = 75,000 \text{ VAR} \]

**Step 3: Calculate Capacitor Bank Value**

To correct the power factor to unity, you need to add 75,000 VAR of capacitive reactive power.

1. **Calculate Capacitive Reactance (X_c):**

\[ X_c = \frac{V^2}{Q_c} = \frac{400^2}{75,000} = \frac{160,000}{75,000} \approx 2.13 \text{ Ω} \]

2. **Calculate Capacitance (C):**

\[ C = \frac{1}{2 \pi \cdot 50 \cdot 2.13} \approx \frac{1}{669.5} \approx 1.495 \text{ mF} \]

So, you would need a capacitor bank with a capacitance of approximately 1.495 millifarads to correct the power factor from 0.8 to unity.

### Summary

To maintain a unity power factor, you need to add a capacitor bank that supplies reactive power equal to the current reactive power of the system. The required capacitance can be calculated based on the system's voltage, frequency, and the reactive power needed.

This method ensures that your power factor correction is accurate and helps in improving the efficiency and performance of your electrical system.
0 like 0 dislike
To calculate the value of a capacitor bank needed to maintain a unity power factor, you'll first need to know the following:

1. **The existing power factor** (pf) of your system.
2. **The total reactive power (Q)** in the system, which is typically measured in kilovars (kVAR).

Here's a step-by-step example:

1. **Determine the Reactive Power (Q):**
   Suppose you have a 500 kVA load with a current power factor of 0.7. The real power (P) is:
   \[ P = 500 \text{ kVA} \times 0.7 = 350 \text{ kW} \]

   The reactive power (Q) can be calculated using the formula:
   \[ Q = P \times \sqrt{\frac{1 - \text{pf}^2}{\text{pf}^2}} \]
   \[ Q = 350 \times \sqrt{\frac{1 - 0.7^2}{0.7^2}} \approx 350 \times \sqrt{\frac{0.51}{0.49}} \approx 350 \times 1.02 \approx 357 \text{ kVAR} \]

2. **Calculate Required Capacitive Reactance (Qc):**
   To correct the power factor to unity (1.0), you need to add enough capacitive reactive power to offset the existing reactive power. Thus, you'll need:
   \[ Q_c = Q \text{ (since we are aiming for unity power factor)} \]
   \[ Q_c = 357 \text{ kVAR} \]

3. **Determine the Capacitor Bank Size:**
   To correct the power factor from 0.7 to 1.0, you need a capacitor bank of approximately 357 kVAR.

In this example, installing a 357 kVAR capacitor bank would bring your power factor to unity, assuming no other changes in the system.
0 like 0 dislike

Related questions

In a 20kVA, 1000/400V, 1f 50Hz transformer, iron and full-load copper losses are 300 W and 500 W respectively. Calculate its efficiency at ¾ full load at unity power factor.
Answer : To calculate the efficiency of the transformer at \(\frac{3}{4}\) full load, we'll follow these steps: 1. **Determine the full-load output power:** The transformer's rated power is 20 kVA. At ... of the transformer at \(\frac{3}{4}\) full load and unity power factor is approximately **96.3%**....

Show More

Calculate the RMS value, form factor, and peak factor of a periodic voltage with given values for equal time intervals.
Answer : To calculate the RMS value, form factor, and peak factor of a periodic voltage, you need to follow specific formulas and procedures. Let's break down each calculation step-by-step. ### ... voltage waveform's characteristics, including its effective value, shape, and peak relative to its RMS value....

Show More

An industrial consumer charged with the scheduled tariff of Rs.250 /kVA per month for maximum demand and 150 paisa per unit consumed for load factor of 60% and 80%. Find overall cost per unit at i) unity P.F. ii) 0.9 P.F. consider maximum demand of 50 kVA.
Answer : To determine the overall cost per unit for an industrial consumer based on the given data, we need to calculate the cost considering both the maximum demand and the energy consumption. Here's how we can ... 1.93/kWh The power factor does not alter the overall cost per unit directly in this case....

Show More

Design an illumination scheme for a workshop with an area of 80 x 20 m in size. Assume a suitable space height ratio, utilization factor, and depreciation factor. Consider a lamp efficiency of 20 lumens/watt.
Answer : Designing an illumination scheme for a workshop involves several steps, including calculating the required illumination level, determining the number of luminaires needed, and choosing the appropriate ... steps, you can ensure adequate lighting for your workshop, improving safety and productivity....

Show More

For the tariff of 125/kVA of maximum demand and 3.00 per unit consumed; load factor = 50%, find overall cost/unit at i) unity power factor ii) 0.8 p.f consider maximum demand = 10 kVA.
Answer : To calculate the overall cost per unit (kWh) for the given tariff structure, we need to use the following steps: ### Given Data: - **Tariff for maximum demand**: ₹125 per kVA of maximum demand - **Tariff per unit consumed ... = **₹3.35** 2. **At power factor 0.8**: Overall cost per unit = **₹3.43**...

Show More
Welcome to Electrical Engineering, where you can ask questions and receive answers from other members of the community.