### Buchholz Relay: Construction and Operation
The
Buchholz relay is a protective device used in
oil-immersed transformers to detect faults such as
internal short circuits or
overheating. It is typically installed in the
conservator tank of a transformer and operates by monitoring the gas and oil flow within the transformer. It helps to detect faults at an early stage and provides a reliable means of protection for large transformers.
Construction of Buchholz Relay
The Buchholz relay consists of the following components:
- Relay Chamber:
- The main body of the relay, which is filled with oil from the transformer.
- Float Mechanism:
- A float is mounted in the relay chamber. This float responds to the rise in oil levels caused by gas generation from internal transformer faults (like short circuits or overheating).
- Contact Points:
- The float is connected to a set of contacts. When the oil level changes (due to gas generation or an oil surge), the float moves, and the contacts either close or open, triggering an alarm or trip signal.
- Gas Detection:
- When a fault occurs inside the transformer, gases such as hydrogen, methane, or ethane are produced. These gases rise to the conservator tank, which causes the Buchholz relay to detect these gases as they flow into the relay chamber.
- Main Gas Pipe:
- The pipe through which the gas from the transformer flows into the Buchholz relay.
- Oil Surge Detection:
- The oil surge caused by faults can also be detected by the movement of the float, which activates the relay to indicate a fault condition.
- Reset Mechanism:
- In case of a fault, the relay can be reset manually after the fault is cleared.
Working Principle and Operation of Buchholz Relay
- Gas Formation:
- When an internal fault occurs in the transformer (such as a short circuit or overheating), it causes the transformer oil to heat up. This heat results in the formation of gases inside the transformer.
- Gas Movement:
- These gases (such as hydrogen and methane) move towards the conservator tank, which is connected to the Buchholz relay. The gas flow enters the relay chamber.
- Float Movement:
- The gas causes the oil level inside the relay chamber to rise, moving the float upward.
- If there is a significant amount of gas (indicating a major fault), the float will trigger the contacts, sending an alarm or trip signal to the protection system.
- Oil Surge:
- In addition to gas formation, faults can cause an oil surge due to the expansion of the transformer oil. This oil surge can move the float and activate the relay, indicating a fault.
- Alarm or Trip Signal:
- The relay has two main stages of operation:
-
Initial Fault (Gas Accumulation): If small amounts of gas accumulate, the relay triggers an
alarm.
-
Severe Fault (Oil Surge or Large Gas Accumulation): If the oil level rises too much due to a large surge or excessive gas accumulation, the relay will
trip the transformer, disconnecting it from the power supply to prevent further damage.
Diagram of Buchholz Relay
Here’s a simple labeled diagram of the Buchholz relay:
`
+-------------------------------+
| Buchholz |
| Relay |
| |
+-----------+-------------------------------+----------+
| |
| Main Gas Pipe |
| |
| +--------------------------+ |
| | Oil Float Chamber | |
| | +----------------|
| | | |
| | +--------------------+ | |
| | | Float | | |
| | | | | |
| | | (Moves with Oil | | |
| | | and Gas Flow) | | |
| | +--------------------+ | |
| | | |
| | Gas Accumulation | |
| | Detection Area | |
| +--------------------------+ |
| |
| +------------------------+ |
| | Contacts for Alarm | |
| | or Trip | |
+-------------+------------------------+-------------------+
Oil Flow
`
Types of Faults Detected by Buchholz Relay
- Minor Faults (Gas Formation):
- Small internal faults produce small amounts of gas. These gases are detected by the Buchholz relay, which then triggers an alarm.
- Major Faults (Oil Surge):
- Large faults, such as short circuits, cause a significant rise in the temperature and the formation of a large amount of gas. This leads to an oil surge that moves the float significantly, triggering the relay to trip the transformer.
Advantages of Buchholz Relay
- Early Detection of Faults: The Buchholz relay detects faults in the early stages, even before a significant transformer failure occurs.
- Prevents Major Damage: By tripping the transformer during severe faults, it helps prevent catastrophic damage to the transformer.
- Sensitive to Gas and Oil Movements: It is sensitive enough to detect minor faults (gas accumulation) and more serious faults (oil surge).
Disadvantages
- Not Suitable for Small Transformers: Buchholz relays are primarily used in large oil-immersed transformers and are not suitable for smaller transformers.
- Requires Regular Maintenance: The relay must be checked and maintained regularly to ensure proper functioning.
---