🔍
Back
A 500kVA distribution transformer having copper and iron losses of 5kW and 3kW respectively on full load. The transformer is loaded as shown below: Loading (kW) Power Factor (Lag) No. of hours 400 0.8 06 300 0.75 12 100 0.8 03 No load - 03 Calculate the all-day efficiency.
0 like 0 dislike

1 Answer

✔️
Best answer
To calculate the all-day efficiency of the transformer, we need to consider the total energy output, the total energy input, and the losses over a 24-hour period. The transformer experiences two types of losses: copper losses (variable) and iron losses (constant).

### Step 1: List out the given data
- **Rated transformer capacity:** 500 kVA
- **Copper losses (at full load):** 5 kW
- **Iron losses (constant):** 3 kW
- **Load profile:**
  - 400 kW for 6 hours with a power factor of 0.8
  - 300 kW for 12 hours with a power factor of 0.75
  - 100 kW for 3 hours with a power factor of 0.8
  - No load for 3 hours

### Step 2: Calculate the losses for each loading condition

#### Copper Losses:
Copper losses are proportional to the square of the load. Therefore, at any given load \( P_L \), the copper losses can be calculated as:

\[
\text{Copper Losses} = \left(\frac{P_L}{500}\right)^2 \times 5 \, \text{kW}
\]

Where 500 kVA is the full-load rating and 5 kW is the copper loss at full load.

#### Iron Losses:
Iron losses are constant at 3 kW, regardless of the load, so they will be the same for all conditions.

### Step 3: Calculate the total losses and output for each period
Now, we'll break it down for each loading condition.

#### For 400 kW load (6 hours):
- Copper losses at 400 kW:
  \[
  \text{Copper Losses} = \left(\frac{400}{500}\right)^2 \times 5 = \left(0.8\right)^2 \times 5 = 3.2 \, \text{kW}
  \]
- Total losses = Copper losses + Iron losses = 3.2 + 3 = 6.2 kW
- Output power = 400 kW

#### For 300 kW load (12 hours):
- Copper losses at 300 kW:
  \[
  \text{Copper Losses} = \left(\frac{300}{500}\right)^2 \times 5 = \left(0.6\right)^2 \times 5 = 1.8 \, \text{kW}
  \]
- Total losses = Copper losses + Iron losses = 1.8 + 3 = 4.8 kW
- Output power = 300 kW

#### For 100 kW load (3 hours):
- Copper losses at 100 kW:
  \[
  \text{Copper Losses} = \left(\frac{100}{500}\right)^2 \times 5 = \left(0.2\right)^2 \times 5 = 0.2 \, \text{kW}
  \]
- Total losses = Copper losses + Iron losses = 0.2 + 3 = 3.2 kW
- Output power = 100 kW

#### For no load (3 hours):
- Copper losses at no load = 0 (since copper losses are proportional to the load)
- Iron losses = 3 kW (constant)
- Total losses = 3 kW
- Output power = 0 kW

### Step 4: Calculate the total energy input and output over 24 hours

- **Total energy output:**
  - For 400 kW load (6 hours):
    \[
    \text{Energy output} = 400 \, \text{kW} \times 6 \, \text{hours} = 2400 \, \text{kWh}
    \]
  - For 300 kW load (12 hours):
    \[
    \text{Energy output} = 300 \, \text{kW} \times 12 \, \text{hours} = 3600 \, \text{kWh}
    \]
  - For 100 kW load (3 hours):
    \[
    \text{Energy output} = 100 \, \text{kW} \times 3 \, \text{hours} = 300 \, \text{kWh}
    \]
  - For no load (3 hours):
    \[
    \text{Energy output} = 0 \, \text{kW} \times 3 \, \text{hours} = 0 \, \text{kWh}
    \]

  **Total energy output** = 2400 + 3600 + 300 + 0 = 6300 kWh

- **Total energy input:**
  The energy input includes the output energy plus the losses.

  - For 400 kW load (6 hours):
    \[
    \text{Energy input} = \text{Energy output} + \text{Losses} = 2400 + (6.2 \times 6) = 2400 + 37.2 = 2437.2 \, \text{kWh}
    \]
  - For 300 kW load (12 hours):
    \[
    \text{Energy input} = 3600 + (4.8 \times 12) = 3600 + 57.6 = 3657.6 \, \text{kWh}
    \]
  - For 100 kW load (3 hours):
    \[
    \text{Energy input} = 300 + (3.2 \times 3) = 300 + 9.6 = 309.6 \, \text{kWh}
    \]
  - For no load (3 hours):
    \[
    \text{Energy input} = 0 + (3 \times 3) = 9 \, \text{kWh}
    \]

  **Total energy input** = 2437.2 + 3657.6 + 309.6 + 9 = 6403.4 kWh

### Step 5: Calculate the all-day efficiency

The all-day efficiency \( \eta_{\text{all-day}} \) is given by:

\[
\eta_{\text{all-day}} = \frac{\text{Total Energy Output}}{\text{Total Energy Input}} \times 100
\]

\[
\eta_{\text{all-day}} = \frac{6300}{6403.4} \times 100 = 98.39\%
\]

### Final Answer:
The all-day efficiency of the transformer is approximately **98.39%**.
0 like 0 dislike

Related questions

A 3 phase line of 4 km length delivers 4000 kW at a p.f of 0.8 lagging to a load the resistance and reactance per km of each conductor are 0.2 Ω and 0.5 Ω respectively if the voltage at the supply end is maintained at 11 kV. Calculate the received end voltage and efficiency of line.
Answer : Let's break down the problem step by step and calculate the received end voltage and the efficiency of the line. ### Given Data: - Power delivered to the load, \( P = 4000 \, \text{kW} \) - Power factor, \( \text{p. ... voltage**: \( 10.43 \, \text{kV} \) - **Efficiency of the line**: \( 98.61\% \)...

View solution
0 like 0 dislike
11 views 1 answer
× Full Screen Image

A plant consists of two 10 MVA generators of reactance 18% each and two 5 MVA generators of 12% each. All are connected to bus bar to supply a load through three step up transformers of 8 MVA each having reactance of 8%. Determine fault MVA on HV side of any one transformer.
Answer : To determine the fault MVA on the high-voltage (HV) side of any one transformer, we need to first calculate the total reactance of the system (the combined reactance of all generators and transformers) and then ... Thus, the fault MVA on the high-voltage side of any one transformer is **8.77 MVA**....

View solution
0 like 0 dislike
16 views 1 answer
× Full Screen Image

A motor has to exert power starting from zero and rising uniformly to 150 HP in 8 mins after which it works at constant power of 100 HP for 5 mins. The motor remains on no load for next 5 mins. The cycle again starts and repeats indefinitely. Determine suitable size of motor.

View solution
0 like 0 dislike
8 views 0 answers
× Full Screen Image

The power input to a 500V 50Hz 6Pole 3 phase induction motor running at 975 rpm is 40 kW. The stator losses are 1kW and friction and windage losses are 2kW. Calculate: (i) Slip (ii) Rotor copper loss (iii) Shaft power (iv) Efficiency

View solution
0 like 0 dislike
14 views 0 answers
× Full Screen Image

A workshop measures 10m × 25m. The shop is illuminated by 24 lamps of 200 watts each. The lumen efficiency of each lamp is 15 lumens per watt. Depreciation factor is assumed to be 0.8 and a coefficient of utilization 0.5. Determine the illumination on the working plane.

View solution
0 like 0 dislike
7 views 0 answers
× Full Screen Image

A three-phase transformer having a line voltage ratio of 0.4 kV/11kV is connected Star/Delta and protective transformers on the 0.4 kV side have a current ratio of 500/5. Calculate the ratio of ... on the 11 kV side. Draw a neat circuit diagram and indicate the given values at appropriate places.

View solution
0 like 0 dislike
9 views 0 answers
× Full Screen Image

Which meter has a greater sensitivity and why? Meter A having a range of 0-10 V and a multiplier resistance of 18 kΩ and meter B with a range of 0-300 V and multiplier resistance of 298 kΩ? Both meter movements have a resistance of 2 kΩ.

View solution
0 like 0 dislike
12 views 0 answers
× Full Screen Image

A single phase AC distributor AB 300 M long is fed from end A and is loaded as under.
Answer : It seems like you're describing a single-phase AC distribution line with a load at the far end (point B) of the 300-meter long line. Could you provide more details about the loading conditions, such ... , or power losses along the line? Let me know the specifics so I can assist you more accurately!...

View solution
0 like 0 dislike
10 views 1 answer
× Full Screen Image

Why power factor of the transformer under no load is very low?
Answer : The power factor of a transformer under no load is very low because the primary current mainly consists of magnetizing current. Here's why: 1. **Magnetizing Current**: When the transformer is on no ... core and not to supply real power to a load, resulting in a high proportion of reactive power....

View solution
0 like 0 dislike
10 views 1 answer
× Full Screen Image

Is a power factor of 0.8 good?
Answer : A power factor of 0.8 means that 80% of the power is being used effectively, and 20% is wasted. In many industrial or commercial settings, a power factor of 0.8 is considered okay but not ... not optimal. Aiming for a power factor closer to 1 is usually preferred for efficiency and cost savings....

View solution
0 like 0 dislike
11 views 1 answer
× Full Screen Image

A 3 φ I.M. has synchronous speed of 250rpm and 4% slip at full load. The rotor has a resistance of 0.02Ω/ph and stand still reactance of 0.15Ω/ph. Calculate i) The speed at which max torque is developed. ii) The ratio of maximum to F. L. torque. iii) The ratio of maximum to starting torque.

View solution
0 like 0 dislike
18 views 0 answers
× Full Screen Image

A 220V/22kV three-phase transformer is connected in star/delta. The protective transformers on the 220V side have a current ratio of 400/5. Calculate the CT ratio on the 22kV side.

View solution
0 like 0 dislike
12 views 0 answers
× Full Screen Image

Plot the chronological load curve and load duration curve. Find the load factor of the plant and energy supplied by the plant in 24 hours.
Answer : To plot the **chronological load curve** and the **load duration curve**, we first need to understand what these curves represent, and how to compute the load factor and energy supplied by ... how the load varies throughout the day and the duration for which different load levels are sustained....

View solution
0 like 0 dislike
13 views 1 answer
× Full Screen Image

Select insulating materials for following parts: (i) Insulation between heating element and base plate of electric iron. (ii) Insulation used over copper or aluminium conductor used for making coils. (iii) Transformer bushings. (iv) Insulation between transmission line and pole.
Answer : Here are the insulating materials typically used for each of the given applications: 1. **Insulation between heating element and base plate of electric iron**: ** ... on their insulating properties, heat resistance, dielectric strength, and ability to withstand environmental conditions....

View solution
0 like 0 dislike
15 views 1 answer
× Full Screen Image

What is the power factor of an alternator at no load?
Answer : At **no load**, the power factor of an alternator is typically **very low**, close to **zero**. This happens because, at no load, the alternator is not supplying any real power (active ... zero. As the load increases, the alternator starts supplying more real power, and the power factor improves....

View solution
0 like 0 dislike
12 views 1 answer
× Full Screen Image

An industrial consumer charged with the scheduled tariff of Rs.250 /kVA per month for maximum demand and 150 paisa per unit consumed for load factor of 60% and 80%. Find overall cost per unit at i) unity P.F. ii) 0.9 P.F. consider maximum demand of 50 kVA.
Answer : To solve this, we need to calculate the total cost of electricity consumption for an industrial consumer, considering the maximum demand (MD), load factor (LF), and power factor (PF) at ... tariff is based on kVA, and the load factor and total consumption determine the cost more significantly....

View solution
0 like 0 dislike
12 views 1 answer
× Full Screen Image

State the effects of low power factor on efficiency and voltage regulation of short transmission lines.
Answer : Low power factor in transmission lines can have a significant impact on the efficiency and voltage regulation of short transmission lines. Here's a breakdown of the effects: ### 1. * ... energy losses and poor voltage control, which reduces the overall performance of the transmission system....

View solution
0 like 0 dislike
12 views 1 answer
× Full Screen Image

A single phase wattmeter rated for 500 V; 5 A is having full scale deflection of 1000 watt. What is multiplying factor of the wattmeter?

View solution
0 like 0 dislike
7 views 0 answers
× Full Screen Image

Draw vector diagram of loaded alternator at lagging power factor.
Answer : To draw the **vector (phasor) diagram of a loaded alternator at lagging power factor**, we need to represent the relationship between the various voltages and currents under this load condition. Here's a ... can generate a labeled vector diagram for you. Would you like me to create and show it now?...

View solution
0 like 0 dislike
9 views 1 answer
× Full Screen Image

Which factor the copper loss of a transformer depends?
Answer : The copper loss in a transformer depends on the following factors: 1. **Load Current (I)**: Copper loss is directly proportional to the square of the load current. The higher the load current, ... the load on the transformer. The more current and resistance you have, the greater the copper loss....

View solution
0 like 0 dislike
11 views 1 answer
× Full Screen Image

Why most of analog o/p devices having o/p range 4 to 20 mA and not 0 to 20 mA?
Answer : The main reason most analog output devices use a 4 to 20 mA range instead of 0 to 20 mA is to ensure reliable operation and easier detection of faults. Here's a breakdown of why 4- ... fault detection, and stability in signal transmission, which is why it's widely adopted in analog output devices....

View solution
0 like 0 dislike
11 views 1 answer
× Full Screen Image

Is a power of 0.8 good?
Answer : Yes, a power factor of 0.8 is generally considered acceptable, though not ideal. Power factor (PF) is a measure of how effectively electrical power is being used. It ranges from 0 to 1: ... factor. To improve the power factor, capacitors or other corrective devices are often added to the system....

View solution
0 like 0 dislike
10 views 1 answer
× Full Screen Image

What should be taken as electrolyte for electroplating of nickel on iron?
Answer : For electroplating nickel on iron, the most commonly used electrolyte is a **nickel sulfate (NiSO₄)** solution, often combined with other chemicals to improve the plating process. A typical electrolyte ... ) and plating time will influence the thickness and quality of the nickel layer on the iron....

View solution
0 like 0 dislike
8 views 1 answer
× Full Screen Image

Sketch a diagram showing interfacing of two chips of RAM having a size of 2k × 8 to the 8051 microcontroller. Write its memory map.
Answer : To interface two 2K 8 RAM chips with an 8051 microcontroller, we will use address lines and control signals to manage the data flow between the microcontroller and the RAM chips. ### Components Required: ... Chip 2. If you have any further questions or need additional details, feel free to ask!...

View solution
0 like 0 dislike
17 views 1 answer
× Full Screen Image

Illustrate the load sharing and isolating technique in transformer to predict energy efficiency.
Answer : Sure! I'll explain **Load Sharing** and **Isolating Technique** in transformers carefully and in detail so that everyone - from beginners to advanced - can easily understand how they affect **energy ... practically implemented? (Just tell me - I can make it even easier with real cases!)...

View solution
0 like 0 dislike
7 views 1 answer
× Full Screen Image

What is the basic loading condition for transformer and its life expectancy?
Answer : ### Basic Loading Condition for Transformers The loading condition of a transformer refers to the amount of electrical load (in terms of power, typically measured in kVA or MVA) that ... , ensuring it operates within its capacity, and minimizing exposure to extreme temperatures and overloads....

View solution
0 like 0 dislike
9 views 1 answer
× Full Screen Image
0 like 0 dislike
10 views 0 answers
× Full Screen Image
0 like 0 dislike
8 views 0 answers
× Full Screen Image

What is the speed variation of the induction motor from no load to full load?

View solution
0 like 0 dislike
10 views 0 answers
× Full Screen Image

A moving coil instrument gives full scale deflection of 24 mA. When a P.D. across if is 108 mV. Find the value of – (i) Series resistance for full scale deflection of 400 V. (ii) Find the power consumption.

View solution
0 like 0 dislike
13 views 0 answers
× Full Screen Image

A uniform illumination of 150 lux is to be obtained on the floor of a room measuring 15m x 15m by arranging electric lights suitably. Calculate the number of lamps and wattage of each ... lamp efficiency is 20 lumens/watt. Assume and write suitable values of constants required for this calculation.
Answer : To solve this lighting problem, we'll follow a step-by-step method using the **lumen method** (also called the **flux method**). The goal is to determine the **number of lamps** and their ** ... --- Would you like me to show this as a diagram or table format for easier presentation to students?...

View solution
0 like 0 dislike
12 views 1 answer
× Full Screen Image

What are the effects of line losses on overall efficiency?
Answer : Line losses in electrical systems refer to the energy lost as electrical power travels through transmission and distribution lines due to the resistance of the conductors. These losses have a ... . This reduces both the economic and environmental efficiency of the entire power distribution network....

View solution
0 like 0 dislike
9 views 1 answer
× Full Screen Image

Why motor are rated as KW while transformer rated in kVA?
Answer : Motors are rated in **kW (kilowatts)**, while transformers are rated in **kVA (kilovolt-amperes)** because of the different ways they handle electrical power and the factors affecting their ... whereas a transformer's capacity is related to its ability to transfer both real and reactive power....

View solution
0 like 0 dislike
14 views 1 answer
× Full Screen Image

State the working principle and operation of automatic power factor controller used in transmission & distribution system.
Answer : **Working Principle and Operation of Automatic Power Factor Controller (APFC) in Transmission and Distribution Systems** ### **Working Principle:** The **Automatic Power Factor Controller (APFC ... and reduces electricity bills. Would you like a diagram to visually represent this operation?...

View solution
0 like 0 dislike
9 views 1 answer
× Full Screen Image

Illustrate the benefits of time off day and peak off day tariff relevant to energy cost along with its impact on energy bill.

View solution
0 like 0 dislike
13 views 0 answers
× Full Screen Image
0 like 0 dislike
7 views 0 answers
× Full Screen Image

State Magneto-striction. Draw Hysteresis loop for: (i) High silicon steel (ii) Copper (iii) Soft iron (iv) Wood.

View solution
0 like 0 dislike
11 views 0 answers
× Full Screen Image

Explain the relation of V2 and I2 based on the load connected to the transformer.
Answer : The relationship between the secondary voltage (\(V_2\)) and the secondary current (\(I_2\)) of a transformer depends on the nature of the load connected to the transformer's secondary side. Let's break ... on the turns ratio, while the current \(I_2\) depends on the type and magnitude of the load....

View solution
0 like 0 dislike
19 views 1 answer
× Full Screen Image

What are the losses in a transformer on what factors do they depend how they are minimized?
Answer : Transformers are crucial components in electrical systems, but like any electrical equipment, they experience some losses during operation. These losses mainly occur due to the inherent properties ... can design more efficient transformers, saving energy and reducing heat generation in the system....

View solution
0 like 0 dislike
11 views 1 answer
× Full Screen Image

How do you calculate transformer losses?
Answer : Transformer losses are typically calculated by considering two main types of losses: 1. **Core Losses (Iron Losses)**: These are the losses that occur in the transformer core, mainly due to hysteresis and eddy ... Power}} = \frac{\text{Output Power}}{\text{Output Power} + \text{Total Losses}} \]...

View solution
0 like 0 dislike
10 views 1 answer
× Full Screen Image

How many kW is 100 kVA?
Answer : To convert kVA (kilovolt-amperes) to kW (kilowatts), you need to know the power factor (PF) of the system, which is usually between 0 and 1. The formula is: \[ \text{kW} = \text{kVA} \times \text{PF ... = \text{80 kW} \] Let me know if you want more details or have a specific power factor in mind!...

View solution
0 like 0 dislike
10 views 1 answer
× Full Screen Image

How to size a 75 kVA transformer?
Answer : Sizing a transformer involves selecting a transformer that can handle the required load and operating conditions without overloading or becoming inefficient. When sizing a 75 kVA transformer, several key ... you will ensure that your transformer is appropriately sized for the load it will handle....

View solution
0 like 0 dislike
12 views 1 answer
× Full Screen Image

Is 0 a yes or no?
Answer : In many contexts, **0** is typically used to represent **no**, and **1** is used to represent **yes**. This is common in binary systems, where 0 and 1 are used to represent two possible states (off/on, ... So, in general, **0** is often associated with **no**, but it depends on how it's being used!...

View solution
0 like 0 dislike
12 views 1 answer
× Full Screen Image

How does a UPS enhance power distribution efficiency?
Answer : A **UPS (Uninterruptible Power Supply)** enhances power distribution efficiency in several key ways: ### 1. **Power Conditioning** A UPS regulates voltage, frequency, and waveform. This ensures that ... network. Would you like a diagram showing how a UPS fits into a power distribution system?...

View solution
0 like 0 dislike
10 views 1 answer
× Full Screen Image

Explain the suitability of copper as an electrical conductor with reference to its mechanical and electrical properties.

View solution
0 like 0 dislike
12 views 0 answers
× Full Screen Image

What is the unit of power work and energy respectively?
Answer : The units of power, work, and energy are as follows: 1. **Power**: The unit of power is the **watt (W)**. - 1 watt = 1 joule per second (J/s). - Power is the rate at which work is done or energy is ... So, to sum it up: - Power: **watt (W)** - Work: **joule (J)** - Energy: **joule (J)**...

View solution
0 like 0 dislike
12 views 1 answer
× Full Screen Image

What will happen when power factor is leading in distribution of power?
Answer : When the power factor is leading in the distribution of power, it means that the current is ahead of the voltage in phase. This situation typically occurs in systems with capacitive loads, like ... can also lead to issues like voltage rise, equipment stress, and instability if not properly managed....

View solution
0 like 0 dislike
11 views 1 answer
× Full Screen Image

How does a basic power factor correction (PFC) circuit improve efficiency?

View solution
0 like 0 dislike
14 views 0 answers
× Full Screen Image

How do inverters enhance the efficiency of power distribution systems?

View solution
0 like 0 dislike
12 views 0 answers
× Full Screen Image

How to minimize copper losses?
Answer : Copper losses, also known as I²R losses, occur in electrical conductors like wires or coils when current flows through them. These losses are caused by the resistance of the conductor and ... these strategies, you can minimize copper losses and improve the efficiency of your electrical system....

View solution
0 like 0 dislike
6 views 1 answer
× Full Screen Image
Learn Electrical and Electronics Engineering the easy way at Electrical-Engineering.app – tutorials, tools, calculators, and video lessons for students, professionals, and beginners.

Subjects

29.4k questions

17.8k answers

8.9k users